PT PLN (Persero) - UIP KITRING NUSA TENGGARA - UPP SUMBAWA

Project Overview

PLTU SUMBAWA BARAT (2X7) MW





Boiler 

Manufactured                         = WUXI HUANGUANG BOILERCO.LTD
Type                                       = Stocker
Output capacity                      = 40 ton / hour
Volume                                   = 30780 L
Working pressure                   = 5,3 Mpa
Design pressure                     = 6,15 Mpa
Hydrostatic test pressure       = 9,22 Mpa
Design temperature               = 510 C


Turbine

Manufactured                         = Hangzhou Chinen Steam Turbine Power CO. LTD
Rated speed                           = 3000 RPM
Rotor material                        = 34CrMo1A (0,86%Cr-Steel)
Casing material                      = ZG17Cr1Mo
Impeler material                     = 34CrMo1A (0,86%Cr-Steel)


Generator

Manufactured                         = Hangzhou Hangfa Electrical Equipment Co . Ltd
Type                                       = QF - K9 - 2 6,3 kV
Rated Output                         = 8.500 kW
Maximum continous output   = 105 %
Speed                                    =  3000 RPM
Rated power factor                = 0,85
Rated freqwensi                     = 50 hZ
Phase                                     = 3
Rated voltage                         = 6300 v
Rated phase current               = 970 A
Pole number                           = 2
Eficiency                                 = 97,3
Cooling system                      = Air cooling


Main Transformer

Manufctured                                   = ASEA BROWN BOVERI  VIETNAM
Type                                                = SPT, 3 phase ,50 Hz, Outdoor, oil immersed
Standard                                         = IEC-60076
Powe rating                                     = 12,5 MVA
Vector group                                    = YNd11
Insulation level                                 = HV : LI 325 AC  140 kV uniform
                                                            LV : li 60 ac 20 kV uniform                                     Impedance voltage                          = HV - LV : 9,4 % BASE ON 12,5 MVA
                                                           HV - LV : 7,5 % BASE ON 10 MVA
System faul level                             = HV - LV : 3 - 0,5 GA
No load current at rated voltage      = 0,3 %
No load loss at rated voltage           =  11 kW according IEC 60076-1
Load Losses at nominal voltage      = HV - LV : 91 Kw base on 12,5 MVA at 75 C
                                                            HV - LV : 58 Kw base on 10 MVA at 75 C
Temp rise top oil / winding                = 60/65 C